Skip to main content

Load Factors - AS/NZS 7000:2016

Load factors in Neara are mapped in the table below to AS/NZS7000. 

Neara Load Factor

AS/NZS Load Factor

Ft

Ftm, Ftw, Fte, Fb

Fc

Always equal to 1.0

Gc

Gc, Sy

Wn

Always equal to 1.0

Gs

Gs, Q

AS/NZS7000 Table 7.1 provides a list of loading conditions that need to be considered for structural analysis. Below is the recommended mapping between the values in Table 7.1 and Neara.

Loading Condition

Ft

Fc

Gc

Wn

Gs

Maximum wind and maximum weight

1.25

1.0

1.25

1.0

1.1

Maximum wind and minimum weight

1.25

1.0

0.0

1.0

0.9

Maximum wind and uplift

1.25

1.0

1.25

1.0

0.9

Everyday condition (sustained loads)

1.1

1.0

1.25

1.0

1.1

Snow and ice

1.1

1.0

1.25

1.0

1.1

Failure containment

1.25

1.0

1.25

1.0

1.1

Serviceability - deflection limit

1.0

1.0

1.1

1.0

1.1

Serviceability - damage limit

1.0

1.0

1.1

1.0

1.1

Maintenance

1.5

1.0

1.5

1.0

1.1

Seismic

1.25

1.0

1.3

1.0

1.0

Did this answer your question?